Prices shown include 22% Italian VAT. The 10% rate applies only to goods for photovoltaic and storage systems, with a declaration from the customer. From outside Italy: pick 22% VAT, or for 0% VAT place the order by bank transfer without paying and we will send a proforma invoice.How VAT works › Delivery in 10-20 daysEastron
Eastron SDM230M Single-Phase Energy Meter — RS485 Modbus, Deye and Solis Compatible
A hybrid inverter without a meter works blind: it does not know how much the house is drawing, so it cannot tell how much energy to keep and how much to export. A bidirectional meter is what makes real self-consumption possible, and on new installations it is also what keeps export within the limit.
The SDM230 connects directly on the line up to 100 A, with no current transformers: two wires in, two out, and the meter is done. Class 1 on active energy, reading up to 999,999.9 kWh, RS485 Modbus RTU with addresses 1 to 247 and up to 64 devices on one bus, which can run 1,000 metres.
At a glance
Product code: SDM230MEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Phase and voltage: single-phase, 230 V (80–120% Un range)Eastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Measurement: direct connection up to 100 AEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Accuracy class: class 1 active energy, class 2 reactiveEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Direction: bidirectional, import and exportEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Technical data
| Specification | Value |
|---|
| Product code | SDM230M |
| Phase and voltage | single-phase, 230 V (80–120% Un range) |
| Measurement | direct connection up to 100 A |
| Accuracy class | class 1 active energy, class 2 reactive |
| Direction | bidirectional, import and export |
| Communication | RS485 Modbus RTU, addresses 1–247, up to 64 devices, bus up to 1,000 m |
| Pulse output | 1000 imp/kWh |
| Operating temperature | −25 … +55 °C |
| Protection rating | IP51, indoor use |
| Standards | IEC 62053-21, EN 50470-1/3 |
| Mounting | DIN rail |