Skip to product information
1 of 1

Jean Müller

Jean Müller KETO-00 NH000/NH00 Fuse Switch-Disconnector 160A 250V DC for Batteries

Jean Müller KETO-00 NH000/NH00 Fuse Switch-Disconnector 160A 250V DC for Batteries

Regular price €59.79
Regular price Sale price €59.79
Sale Sold out Excl. VAT — calculated in the cart
See the price with VAT

Price including VAT by delivery country

  • Italy22% €72.94
  • Germany19% €71.15
  • France20% €71.74
  • Austria20% €71.74
  • Belgium21% €72.34
  • Bulgaria20% €71.74
  • Croatia25% €74.73
  • Cyprus19% €71.15
  • Czech Republic21% €72.34
  • Denmark25% €74.73
  • Estonia24% €74.13
  • Finland25.5% €75.03
  • Greece24% €74.13
  • Hungary27% €75.93
  • Ireland23% €73.54
  • Latvia21% €72.34
  • Lithuania21% €72.34
  • Luxembourg17% €69.95
  • Malta18% €70.55
  • Netherlands21% €72.34
  • Poland23% €73.54
  • Portugal23% €73.54
  • Romania21% €72.34
  • Slovakia23% €73.54
  • Slovenia22% €72.94
  • Spain21% €72.34
  • Sweden25% €74.73

Shown prices exclude VAT. At checkout the rate of the delivery country applies. Businesses with a valid EU VAT number buy without VAT (reverse charge).

  • Prices exclude VAT: tax is calculated in the cart based on the delivery country.
  • EU businesses: 0% VAT with a VAT number valid in VIES — the field appears at checkout, below the delivery address.
  • Reduced 10% VAT on solar and storage for customers in Italy: write to us before ordering.

AVAILABILITY

55 units at this price

Shipping

  • Italy: €13 on orders up to €150, free shipping over €150.
  • European Union: 60 € per order, with no threshold

Rates apply to the cart total and are confirmed at checkout, where shipping to countries outside the EU is also calculated.

View full details
Delivery in 10-20 daysJean Müller

Jean Müller KETO-00 NH000/NH00 Fuse Switch-Disconnector 160A 250V DC for Batteries

The KETO-00 is the fuse switch-disconnector you use to isolate and protect the DC side of a storage system: it sits between the battery bank and the inverter and lets you open the circuit safely, by hand, for maintenance or in an emergency. Inside it carries the NH fuse links, which are the actual protection against short circuit and overload.

This is the bare body: links are not included and are ordered separately, two of them, one on the positive pole and one on the negative. Size them on the battery’s maximum charge and discharge current with a safety margin, not on inverter power. The KETO-00 accepts NH000 and NH00 links up to 160A and works to 250V DC, which covers every 48V and 51.2V battery bank, single or paralleled.

Jean Müller specifies M8 flat terminals for 25mm² to 95mm² cable, 106mm width and a 195mm system size: baseplate or wall mounting, or DIN rail with the retrofit kit. Conditional short-circuit current is 120kA at 500V, impulse withstand 8kV, operating range -25°C to +70°C. The range is moving from blue to black, so either version may ship. Installation is a job for a qualified electrician.

Key strengths

Isolation and protection in oneLoad-break switch plus NH fuse holder for the DC side.
160A up to 250V DCCovers 48V and 51.2V banks, single or paralleled.
NH000 and NH00 linksChosen on real battery current, two per installation.
25mm² to 95mm² cableM8 flat terminals, from the Jean Müller catalogue.
106mm wideBaseplate or wall, or DIN rail with the retrofit kit.

Technical specifications

Feature Value
Product code KETO-00
Jean Müller article no. T500113002
Catalogue designation KETO-00-3/F (Jean Müller data)
Manufacturer Jean Müller
Type NH fuse switch-disconnector, body without fuse links
Fuse size accepted NH000 and NH00 (Jean Müller data)
Rated current 160A
Rated AC voltage 690V (Jean Müller data)
Rated DC voltage 250V DC
Number of poles 3 (Jean Müller data); on DC two are used, positive and negative
Fuse links required 2, ordered separately
Terminals M8/2xM5 flat terminal for 25mm² to 95mm² cable (Jean Müller data)
Width 106mm
System size 195mm
Mounting wall/baseplate, DIN rail with the retrofit kit, or 60mm busbar system (Jean Müller data)
Degree of protection IP20 at the front with the device fitted (Jean Müller data)
Impulse withstand voltage 8kV (Jean Müller data)
Conditional short-circuit current 120kA at 500V, 100kA at 690V (Jean Müller data)
Operating temperature -25°C to +70°C (Jean Müller data)
Standards DIN EN 60947-3; NH fuse links to DIN VDE 0636-2
Colour moving from blue to black: both versions may ship during the changeover
Weight 0.72kg