Jean Müller KETO-00 NH000/NH00 Fuse Switch-Disconnector 160A 250V DC for Batteries
The KETO-00 is the fuse switch-disconnector you use to isolate and protect the DC side of a storage system: it sits between the battery bank and the inverter and lets you open the circuit safely, by hand, for maintenance or in an emergency. Inside it carries the NH fuse links, which are the actual protection against short circuit and overload.
This is the bare body: links are not included and are ordered separately, two of them, one on the positive pole and one on the negative. Size them on the battery’s maximum charge and discharge current with a safety margin, not on inverter power. The KETO-00 accepts NH000 and NH00 links up to 160A and works to 250V DC, which covers every 48V and 51.2V battery bank, single or paralleled.
Jean Müller specifies M8 flat terminals for 25mm² to 95mm² cable, 106mm width and a 195mm system size: baseplate or wall mounting, or DIN rail with the retrofit kit. Conditional short-circuit current is 120kA at 500V, impulse withstand 8kV, operating range -25°C to +70°C. The range is moving from blue to black, so either version may ship. Installation is a job for a qualified electrician.
Key strengths
Technical specifications
| Feature | Value |
|---|---|
| Product code | KETO-00 |
| Jean Müller article no. | T500113002 |
| Catalogue designation | KETO-00-3/F (Jean Müller data) |
| Manufacturer | Jean Müller |
| Type | NH fuse switch-disconnector, body without fuse links |
| Fuse size accepted | NH000 and NH00 (Jean Müller data) |
| Rated current | 160A |
| Rated AC voltage | 690V (Jean Müller data) |
| Rated DC voltage | 250V DC |
| Number of poles | 3 (Jean Müller data); on DC two are used, positive and negative |
| Fuse links required | 2, ordered separately |
| Terminals | M8/2xM5 flat terminal for 25mm² to 95mm² cable (Jean Müller data) |
| Width | 106mm |
| System size | 195mm |
| Mounting | wall/baseplate, DIN rail with the retrofit kit, or 60mm busbar system (Jean Müller data) |
| Degree of protection | IP20 at the front with the device fitted (Jean Müller data) |
| Impulse withstand voltage | 8kV (Jean Müller data) |
| Conditional short-circuit current | 120kA at 500V, 100kA at 690V (Jean Müller data) |
| Operating temperature | -25°C to +70°C (Jean Müller data) |
| Standards | DIN EN 60947-3; NH fuse links to DIN VDE 0636-2 |
| Colour | moving from blue to black: both versions may ship during the changeover |
| Weight | 0.72kg |