Businesses and non-Italian private customers: purchase with 22% VAT. The 10% rate is reserved for private customers resident in Italy — find out more.
Foreign companies entitled to 0% VAT: please write to info@litio.store.
Eastron SDM72D-M V2 Energy Meter Three-Phase 100 A Modbus RS485 MID
The Eastron SDM72D-M V2 is a three-phase direct measurement energy meter up to 100 A, designed for mounting on a 35 mm DIN rail inside electrical panels. It takes up 4 modules and measures total active energy with bidirectional counting (energy imported from the grid and energy exported), as well as the voltage, current and power of each phase.
In photovoltaic and storage systems it is used as a grid exchange meter: the RS485 port with Modbus RTU protocol makes it possible to send the measurements to the inverter, to a data logger or to a supervision system, enabling functions such as self-consumption control and export limitation. It also features a pulse output of 1000 imp/kWh and a resettable partial counter. The model is MID certified according to Directive 2014/32/EU, so it can also be used for billing.
Key features
Technical specifications
| Feature | Value |
|---|---|
| Product code | EASTRON_SDM72D-MV2 |
| Model | SDM72D-M V2 (SDM72D-M-2) |
| Phases | Three-phase 3P4W (also suitable for 2P3W) |
| Rated voltage | 3 × 230/400 V ac (operating range 80–120% of Un) |
| Nominal current | 10 A reference, 100 A maximum (Imax) |
| Measurement type | Direct, without current transformers |
| Accuracy class | Better than Class 1 / Class B |
| Certification | MID – Directive 2014/32/EU |
| Measured quantities | Total, imported and exported active energy, voltage, current and power per phase, total power |
| Communication | RS485 half-duplex, Modbus RTU, 1200/2400/4800/9600 bps (up to 64 devices on the bus) |
| Pulse output | 1000 imp/kWh |
| Mounting | 35 mm DIN rail, 4 modules (72 mm) |
| Protection rating | IP51 (indoor use) |
| Operating temperature | da -25 °C a +55 °C |
| Dimensions | 72 × 66 × 100 mm |
| Weight | 0.3 kg |
Documentation
PDFDatasheet EASTRON_SDM72D-MV2Official manufacturer documentInstallation and wiring must be carried out by qualified personnel in accordance with the applicable standards and the electrical design of the system.