Skip to product information
1 of 1

GoodWe

GoodWe GW40K-ET-10 Hybrid Inverter 40 kW Three-Phase

GoodWe GW40K-ET-10 Hybrid Inverter 40 kW Three-Phase

Regular price €4,257.21
Regular price Sale price €4,257.21
Sale Sold out
Tax included.

Shipping

  • Italy: €13 on orders up to €150, free shipping over €150.
  • European Union: €60 on orders up to €350, free shipping over €350.

Rates apply to the cart total and are confirmed at checkout, where shipping to countries outside the EU is also calculated.

Scegli IVA
View full details
VAT note
Businesses and non-Italian private customers: purchase with 22% VAT. The 10% rate is reserved for private customers resident in Italy — find out more.
Foreign companies entitled to 0% VAT: please write to info@litio.store.
Delivery in 10-20 daysHybrid On-GridThree-phaseGoodWe

GoodWe GW40K-ET-10 Hybrid Inverter 40 kW Three-Phase

The GoodWe GW40K-ET-10 is the 40 kW three-phase hybrid inverter of the ET 40-50 kW series, intended for commercial and industrial applications with high-voltage storage. It integrates 3 MPPTs with 2 strings each and input currents up to 42 A per tracker, a maximum PV voltage of 1,000 V and a very wide MPPT range (165-850 V), for a photovoltaic array of up to 60,000 W.

The battery works in the 200-800 V range with 100 A continuous in charge and discharge and up to 44,000 W of power. The back-up output delivers a rated 40,000 W with an overload of up to 44,000 VA (48,000 VA for 60 s, 60,000 VA for 10 s), ensuring service continuity for critical loads. Maximum efficiency is 98.1% (97.5% European), the protection rating is IP66 and cooling is by smart fans. Communications include RS485, Wi-Fi, LAN and Bluetooth as standard, with optional 4G, and CAN to the BMS; Type II DC surge arresters (Type I+II optional) and Type II AC surge arresters are built in.

Key features

Commercial power40 kW three-phase with high-voltage storage and up to 60,000 W of photovoltaic array.
3 high-current MPPTsInput currents up to 42 A per tracker and extended MPPT range 165-850 V, compatible with the latest generation of modules.
100 A battery200-800 V range with 100 A continuous in charge and discharge, up to 44,000 W of storage power.
Backup with strong overloadEmergency output of a rated 40,000 W, up to 44,000 VA (48,000 VA for 60 s, 60,000 VA for 10 s).
Complete protectionsType II DC SPD (Type I+II optional) and Type II AC SPD, DC switch, optional AFCI, remote shutdown.
Industrial connectivityRS485, Wi-Fi, LAN and Bluetooth as standard, optional 4G, CAN to the BMS; IP66 for outdoor installation.

Technical specifications

FeatureValue
Product codeGW40K-ET-10
ModelGW40K-ET-10
Rated AC power40.000 W
Max AC power40.000 VA
Recommended max PV power60.000 W
Max PV voltage1.000 V
Start-up voltage200 V
MPPT range165-850 V
Rated PV voltage620 V
Number of MPPTs3
Strings per MPPT2
Max current per MPPT42 / 32 / 42 A
Max short-circuit current per MPPT55 / 42 / 55 A
Battery typeLithium, high voltage
Battery voltage500 V nominal (range 200-800 V)
Number of battery inputs1
Max charge/discharge current100 A / 100 A
Max charge/discharge power44.000 W / 44.000 W
Backup/EPS power40,000 VA rated - max 44,000 VA (48,000 VA for 60 s, 60,000 VA for 10 s)
Max backup current66,7 A @ 380 V / 63,8 A @ 400 V
Grid phaseThree-phase
Grid voltage380/400 V (3L/N/PE), range 176-276 V
Grid frequency50/60 Hz (45-55 / 55-65 Hz)
Max AC current to the grid60,6 A @ 380 V / 58,0 A @ 400 V
Power factor~1 (0.8 leading - 0.8 lagging)
Total harmonic distortion< 3 %
Maximum efficiency98.1 %
European efficiency97.5 %
Max battery-to-AC efficiency97.7 %
MPPT efficiency99.0 %
Surge arrestersDC Type II (Type I+II optional), AC Type II
AFCIOptional
Protection ratingIP66
CoolingSmart fans (smart fan cooling)
CommunicationRS485, Wi-Fi + LAN + Bluetooth, 4G + Bluetooth (optional), CAN (BMS)
User interfaceLED, app via WLAN
Night-time consumption< 15 W
Operating temperature-35 °C ... +60 °C
Relative humidity0-95 %
Max altitude4.000 m
Dimensions (W x H x D)520 x 660 x 260 mm
Weight62 kg
Warranty5 years (GoodWe limited warranty for commercial and industrial inverters)

Documentation

PDFDatasheet GW40K-ET-10Official manufacturer document

String sizing must respect the MPPT voltage and current limits and the electrical design of the system. Installation and grid connection must be carried out by qualified personnel in accordance with the applicable standards.