Businesses and non-Italian private customers: purchase with 22% VAT. The 10% rate is reserved for private customers resident in Italy — find out more.
Foreign companies entitled to 0% VAT: please write to info@litio.store.
Huawei DTSU666-H Three-Phase Meter Smart Power Sensor 100 A with 3 Split-Core CTs
The Huawei DTSU666-H in the 100 A version is the three-phase Smart Power Sensor for photovoltaic systems and storage systems with Huawei SUN2000 inverters. It measures voltage, current, active and reactive power, power factor and energy on the three phases in real time, distinguishing the energy drawn from the grid from the energy fed into it.
It is installed in the distribution board on a 35 mm DIN rail at the connection point and communicates with the inverter via RS485 with Modbus-RTU protocol. Measurement is indirect through three 100 A split-core current transformers with a 40 mA secondary, which are clamped onto the phase cables without having to cut them. It enables self-consumption management, export limitation and monitoring of energy flows in FusionSolar.
Key features
Technical specifications
| Feature | Value |
|---|---|
| Product code | DTSU_100A |
| Model | DTSU666-H 100 A |
| Phases | Three-phase (3P4W / 3P3W) |
| Rated voltage | 230 V AC / 400 V AC, 50/60 Hz |
| Nominal current | 0 – 100 A |
| Measurement type | Indirect with 3 split-core CTs 100 A / 40 mA (included) |
| Accuracy class | Class 1 (active energy) |
| Communication | RS485, Modbus-RTU protocol (4800 / 9600 bps, default 9600) |
| Energy reading range | 0,00 kWh – 999999,9 kWh |
| Own power consumption | ≤ 1.5 W / 6 VA (voltage circuit); ≤ 0.2 – 0.4 VA (current circuit) |
| Mounting | 35 mm DIN rail |
| Operating temperature | −25 °C … +60 °C |
| Relative humidity | ≤ 75 % |
| Protection rating | Not stated by the manufacturer |
| Dimensions | 72 × 100 × 66 mm |
| Weight | 0.4 kg |
Documentation
PDFDatasheet DTSU_100AOfficial manufacturer documentInstallation and wiring must be carried out by qualified personnel in accordance with the applicable standards and the electrical design of the system.