Delivery in 10-20 daysMetering & sensorsAC sideFoxESS

FoxESS DDSU666 Energy Meter Single-Phase 60 A RS485 Modbus

The FoxESS DDSU666 is a single-phase (1P2W) direct measurement energy meter up to 60 A, manufactured by CHINT for single-phase FoxESS inverters. It is installed on a 35 mm DIN rail in the electrical panel, downstream of the utility meter, and measures the energy flows to and from the grid bidirectionally.

Connected to the inverter through the RS485 port with Modbus protocol, it provides the power exchanged with the grid in real time: it is the component that enables the self-consumption monitoring, battery charge/discharge management and export limitation (zero export) functions. Accuracy class 1 guarantees an error within ±1% on current, power and energy.

Key features

Direct measurement up to 60 ASingle-phase direct connection without current transformers, suited to residential systems.
Bidirectional readingMeasures the energy drawn and the energy fed into the grid separately, the basis for calculating self-consumption.
RS485 Modbus communicationCommunicates with the FoxESS inverter at 9600 baud for real time power regulation.
Export controlAllows the inverter to limit or zero the energy fed into the grid according to the network operator's requirements.
Accuracy class 1Error within ±0.5% on voltage and within ±1% on current, power and energy.
DIN rail mountingCompact 2 module format for direct installation in the electrical panel.

Technical specifications

FeatureValue
Product codeZTY0.464.1264
ModelDDSU666 (CHINT for FoxESS)
PhasesSingle-phase 1P2W
Nominal current0–60 A
Measurement typeDirect, without current transformers
Accuracy classClass 1 (±0.5% voltage, ±1% current/power/energy)
Operating voltage176–288 V c.a.
CommunicationRS485, Modbus, 9600 baud
Mounting35 mm DIN rail
Dimensions88 × 70 × 65 mm
Body dimensions (FoxESS datasheet)36 × 85 × 66 mm
Weight0.2 kg