Prices shown include 22% Italian VAT. The 10% rate applies only to goods for photovoltaic and storage systems, with a declaration from the customer. From outside Italy: pick 22% VAT, or for 0% VAT place the order by bank transfer without paying and we will send a proforma invoice.How VAT works › Delivery in 10-20 daysEastron
Eastron SDM120CTM Single-Phase Energy Meter — RS485 Modbus, Deye and Solis Compatible
A hybrid inverter without a meter works blind: it does not know how much the house is drawing, so it cannot tell how much energy to keep and how much to export. A bidirectional meter is what makes real self-consumption possible, and on new installations it is also what keeps export within the limit.
The SDM120CT measures through an external current transformer instead of direct connection: that is what you need when the line is already wired and you do not want to cut it, or when the cable is too thick to enter the meter. Same RS485 Modbus RTU protocol, same accuracy class, one DIN module wide.
At a glance
Product code: SDM120CTMEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Phase and voltage: single-phase, 230 V (80–120% Un range)Eastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Measurement: via external CTEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Accuracy class: class 1 active energy, class 2 reactiveEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Direction: bidirectional, import and exportEastron is one of the European references for DIN-rail meters: its SDM range is what you find in distribution boards across half the continent.
Technical data
| Specification | Value |
|---|
| Product code | SDM120CTM |
| Phase and voltage | single-phase, 230 V (80–120% Un range) |
| Measurement | via external CT |
| Accuracy class | class 1 active energy, class 2 reactive |
| Direction | bidirectional, import and export |
| Communication | RS485 Modbus RTU, addresses 1–247, up to 64 devices, bus up to 1,000 m |
| Pulse output | 1000 imp/kWh |
| Operating temperature | −25 … +55 °C |
| Protection rating | IP51, indoor use |
| Standards | IEC 62053-21, EN 50470-1/3 |
| Mounting | DIN rail |