Businesses and non-Italian private customers: purchase with 22% VAT. The 10% rate is reserved for private customers resident in Italy — find out more.
Foreign companies entitled to 0% VAT: please write to info@litio.store.
Noark 108367 Ex9L-N RCCB 4P 63 A 100 mA Type A
The Noark 108367 is a pure residual current circuit breaker (RCCB) of the Ex9L-N series in a four-pole version, with a rated current of 63 A and a rated residual current of 100 mA, Type A. It takes up 4 modules on the DIN rail and has a rated conditional short-circuit current of 6 kA.
The 63 A size makes it suitable for the role of main residual current device in a three-phase board, upstream of several lines that are already individually protected. The 100 mA threshold is an intermediate choice: it ensures protection against indirect contact and against the risk of fire caused by earth faults, but is less prone than a 30 mA device to nuisance tripping caused by the sum of the natural leakage currents of many loads in parallel. Type A guarantees tripping even with pulsating unidirectional residual current components. Operation is independent of the mains voltage. Being a pure RCCB it does not protect against overload and short circuit and always requires coordination with miniature circuit breakers.
Key features
Technical specifications
| Feature | Value |
|---|---|
| Product code | 108367 |
| Device type | Modular pure residual current circuit breaker (RCCB), Ex9L-N series |
| System side | Alternating current (AC) |
| Number of poles / phases | 4 poles (three-phase 3P+N) |
| Nominal current | 63 A |
| Rated residual current | 100 mA (0,1 A) |
| RCD type | Type A |
| Rated voltage (Ue) | 400 V AC (230 V phase-to-neutral) |
| Rated frequency | 50 Hz |
| Conditional short-circuit current | 6 kA |
| Miniature circuit breaker (MCB) | Not included (pure RCD, to be combined with MCBs) |
| Number of DIN modules | 4 |
| Flush-mounting depth | 72 mm |
| Protection rating | IP20 |
| Mounting | 35 mm DIN rail |
| Dimensions | 79 × 88 × 72 mm |
| Weight | 0.22 kg |
| Standards | IEC/EN 61008-1 (residual current devices without integral overcurrent protection) |
Installation and wiring must be carried out by qualified personnel in accordance with the applicable standards and the electrical design of the system.