Businesses and private customers outside Italy: purchase with 22% VAT. The 10% VAT rate is reserved for private customers resident in Italy — learn more.
Foreign businesses entitled to 0% VAT: write to info@litio.store.
Italy: €120.European Union: €350.
Deye 61.36 kWp Solar Kit with 61.44–122.88 kWh Battery – 50 kW Three-Phase Hybrid Inverter, Commercial/Industrial
Scalable solution for commercial and industrial sites, built to maximise self-consumption
🚚 Delivery in 10–20 days for modules, inverter and storage; the AC (with CEI 0-21 interface protection) and DC protection panels have a 3–4 month lead time.
Commercial & Industrial Solar Kit
Three-phase hybrid PV system for grid-connected operation with energy management, storage and backup, designed around the Deye SUN-50K-SG01HP3-EU inverter, for commercial applications.
| ☀️ 61.36 kWp Solar | 🔋 61.44–122.88 kWh Storage | ⚡ 50 kW Inverter | 🔌 Three-Phase Hybrid |
Kit Contents
104× 590 W N-Type TOPCon bifacial double-glass Silver Frame modules
for a total output of 61.36 kWp.
1× Deye SUN-50K-SG01HP3-EU-BM4 50 kW Three-Phase
Selectable storage:
Deye BOS-G-Pack5.1 LiFePO4 5.12 kWh 51.2 V with BOS-G-PDU-2 PRO PDU/BMS and 3U-HRack-2G rack cabinet included — 61.44 kWh (12 modules, 1 PDU/BMS and 1 rack) or 122.88 kWh (24 modules in two systems of 12, each with its own PDU/BMS and rack, one for each of the two battery inputs).
1× Three-phase PV AC panel 50 kW 100 A with adjustable RCD and SPI, IP65
Protection and isolation of the AC grid connection.
1× PV DC panel 8 strings 8 MPPT 1000 V 32 A with 8 SPDs, IP66
Protection and isolation of the PV strings on the DC side.
PV String Design
Calculated configuration: 8 strings of 13 modules, 2 on each of the 4 MPPTs. Operating voltage Vmp 576.6 V, Voc at 25 °C 686.7 V, conservative Voc at −25 °C 783 V — within the inverter’s 1000 V limit and within the 150–850 V MPPT window. Maximum current per MPPT 26.6 A. Module used: 590 W N-Type TOPCon bifacial double-glass module (Vmp 44.35 V, Voc 52.82 V, Imp 13.30 A; conservative coefficient −0.28 %/°C). DC/AC oversizing ratio: 1.23×. Preliminary configuration: to be re-checked against the datasheet of the revision actually purchased and the site conditions.
Storage, Grid and Operation
- ✓Grid-connected operation with storage and energy flow management.
- ✓LiFePO₄ batteries.
- ✓Deye BOS-G system: 3 to 12 modules in series per BOS-G-PDU-2 PRO PDU/BMS, installed in the 3U-HRack-2G rack cabinet; CAN communication with the inverter. With 12 modules per system the nominal voltage is 614.4 V, within the 160–800 V battery range of the inverter, which has two battery inputs.
A consistent, well-engineered system
The kit uses selected components and a PV configuration sized to the inverter’s electrical limits, for a robust, consistent commercial or industrial system ready for installation by qualified personnel. The kit includes only the specified PV panels, inverter, storage battery/batteries, and AC and DC protection panels. Mounting structures, cables, connectors and installation are not included and must be sized by the installer to suit the site. Installation and grid connection must be carried out by licensed personnel.