Skip to product information
1 of 1

Phoenix Contact

DC Surge Protective Device Type 2 Phoenix Contact 2800642 VAL-MS 600DC-PV/2+V

DC Surge Protective Device Type 2 Phoenix Contact 2800642 VAL-MS 600DC-PV/2+V

Regular price €67.39
Regular price Sale price €67.39
Sale Sold out Excl. VAT — calculated in the cart
  • Prices exclude VAT: tax is calculated in the cart based on the delivery country.
  • EU businesses: 0% VAT with a VAT number valid in VIES — the field appears at checkout, below the delivery address.
  • Reduced 10% VAT on solar and storage for customers in Italy: write to us before ordering.

AVAILABILITY

Currently out of stock at our supplier

Shipping

  • Italy: €13 on orders up to €150, free shipping over €150.
  • European Union: 60 € per order, with no threshold

Rates apply to the cart total and are confirmed at checkout, where shipping to countries outside the EU is also calculated.

View full details
Delivery in 10-20 daysProtection deviceDC sidePhoenix Contact

DC Surge Protective Device Type 2 Phoenix Contact 2800642 VAL-MS 600DC-PV/2+V

The Phoenix Contact VAL-MS 600DC-PV/2+V surge protective device (article number 2800642) is a Type 2 (class II) surge limiter designed specifically for the direct current side of photovoltaic systems up to 800 V DC of continuous operating voltage. It is installed on a 35 mm DIN rail inside the DC combiner box, between the photovoltaic generator and the inverter, and protects the modules, the string cables and the inverter's MPPT input against surges induced by indirect lightning strikes and by switching operations.

The device uses the classic Y configuration (2+V) with three protection paths — L+ / L−, L+ / PE and L− / PE — built with varistors and a series spark gap, a solution that eliminates the leakage current to earth under normal conditions. It consists of a 3-position base with pluggable, thermally monitored protection elements: each cartridge carries an optical status indicator that shows when the element has reached its end of life and must be replaced, without having to dismantle the wiring. The failure behaviour is open circuit (Open-Circuit Mode).

Key features

Type 2 protection for PV stringsIt limits surges of indirect atmospheric and switching origin on the DC side, protecting modules, cables and the inverter's MPPT inputs.
Operating voltage up to 800 V DCThe Ucpv of 800 V DC covers photovoltaic strings with a rated open-circuit voltage of up to 600 V DC.
Three-path Y configurationThe L+/L−, L+/PE and L−/PE paths with a series spark gap eliminate the leakage current to earth in normal service.
Pluggable cartridges with optical indicationThe three thermally monitored protection elements are plug-in replaceable and show their status with an optical indicator on each module.
Nominal discharge 15 kA, maximum 40 kAIn of 15 kA and Imax of 40 kA (8/20 µs) with a protection level Up ≤ 2.7 kV.
DIN rail mounting inside the box53.4 mm wide on a 35 mm rail, M5 screw terminals up to 35 mm², IP20 rating with all terminals occupied.

Technical specifications

FeatureValue
Product code2800642
Product typeSurge protective device (SPD) for photovoltaic systems
System sideDirect current (DC), between the PV generator and the inverter
Brand and modelPhoenix Contact VAL-MS 600DC-PV/2+V — item no. 2800642
Surge protective device (type)Type 2 / class II (PV II according to EN 50539-11)
Maximum continuous operating voltage Ucpv800 V DC
Nominal discharge current In (8/20 µs)15 kA
Maximum discharge current Imax (8/20 µs)40 kA
Protection level Up≤ 2,7 kV
Protection modes3 (L+ / L−, L+ / PE, L− / PE) — Y "2+V" configuration
Protective devices3 thermally monitored pluggable cartridges, with optical status indication on each module
Failure modeOpen circuit (Open-Circuit Mode, OCM)
Mounting35 mm DIN rail (3-position base)
Connection cross-sectionFrom 1.5 to 35 mm² rigid (M5 screw terminals)
Protection ratingIP20 (with all terminals occupied)
Operating temperatureFrom −40 °C to +80 °C
ColourJet black RAL 9005
Dimensions53.40 × 90.00 × 65.50 mm
Weight0.31 kg
StandardsEN 50539-11