Skip to product information
1 of 1

Phoenix Contact

Phoenix Contact 1791818 Surge Protective Device Type 2 275 V 3+1 Pluggable

Phoenix Contact 1791818 Surge Protective Device Type 2 275 V 3+1 Pluggable

Regular price €108.23
Regular price Sale price €108.23
Sale Sold out Excl. VAT — calculated in the cart
  • Prices exclude VAT: tax is calculated in the cart based on the delivery country.
  • EU businesses: 0% VAT with a VAT number valid in VIES — the field appears at checkout, below the delivery address.
  • Reduced 10% VAT on solar and storage for customers in Italy: write to us before ordering.

AVAILABILITY

Product available, quantity not tracked

Shipping

  • Italy: €13 on orders up to €150, free shipping over €150.
  • European Union: 60 € per order, with no threshold

Rates apply to the cart total and are confirmed at checkout, where shipping to countries outside the EU is also calculated.

View full details
Delivery in 10-20 daysProtection deviceAC sidePhoenix Contact

Phoenix Contact 1791818 Surge Protective Device Type 2 275 V 3+1 Pluggable

The Phoenix Contact VAL-SPP-T2-275-3+1-UT/32 (item 1791818) is a Type 2 / Class II surge protective device (SPD) with pluggable protective modules. It is built in the 3+1 configuration, designed for three-phase five-wire networks with separate neutral and PE (L1, L2, L3, N, PE), hence for TT and TN-S systems.

It is installed in the three-phase distribution board, downstream of any Type 1 arrester, to limit transient surges of indirect atmospheric origin and those generated by grid switching operations, protecting household appliances, electronic equipment, inverters and automation panels. In the 3+1 configuration the three phase varistors discharge to the neutral and a gas discharge tube connects the neutral to the protective conductor: this achieves a low protection level without permanent leakage current to earth. Each protection path is provided by a pluggable module with an optical status indicator, which allows the single exhausted module to be replaced without touching the wiring.

Key features

Pluggable protective modulesThe protective plugs are pulled out of the base without touching the wiring, reducing replacement after a discharge event to a few seconds.
3+1 configurationThree L-N varistors plus one N-PE gas discharge tube: a layout suited to TT and TN-S networks, with a low protection level and no permanent leakage current to earth.
Type 2 / Class IIProtection against surges induced by indirect lightning strikes and by grid switching operations, to be installed in the distribution board.
Uc 275 V ACMaximum continuous operating voltage suited to 230/400 V networks with a ±10% tolerance.
Optical status indicatorEach module visually indicates that the varistor is exhausted and needs replacing.
Base with generous screw terminalsThe base accepts large cross-sections, compatible with the low-impedance connecting conductors required by SPDs.

Technical specifications

FeatureValue
Product code1791818
Device typeModular surge protective device (SPD) with plug-in modules, VAL-SPP series
System sideAlternating current (AC)
Surge protective device (type)Type 2 / Class II
Configuration3+1 (L1, L2, L3, N, PE) for TT and TN-S systems
Number of poles / phasesThree-phase + neutral (4 modules)
Rated grid voltage240/415 V AC ±10%, 50/60 Hz
Maximum continuous operating voltage (Uc)275 V AC (L-N e L-PE), 305 V AC (N-PE)
Protection level (Up) L-N≤ 1,35 kV
Protection level (Up) N-PE≤ 0,5 kV
Nominal discharge current (In 8/20 µs)20 kA
Maximum discharge current (Imax 8/20 µs)40 kA
Protected pathsL-N, L-PE, N-PE
Replaceable modulesYes, pluggable protection modules
IndicationOptical status indicator on each module
Protection ratingIP20
Operating temperatureFrom -40 °C to +85 °C
Mounting35 mm DIN rail
Dimensions71.5 × 96.6 × 71.2 mm
Weight0.43 kg
StandardsIEC 61643-11, EN 61643-11:2012+A11:2018

Installation and wiring must be carried out by qualified personnel in accordance with the applicable standards and the electrical design of the system.