How VAT works ›
Siemens 5SD7483-6 DC surge arrester Type 1+2, 1000 V, for photovoltaics
The 5SD7483-6 is the combined Type 1+2 arrester of the SENTRON range for the DC side of a photovoltaic system: it protects inverter and wiring from both direct lightning discharge and induced surges.
It works up to 1000 V DC with an impulse current of Iimp 5 kA (10/350 µs), a nominal discharge current of In 15 kA and a maximum of 40 kA (8/20 µs), holding the protection level at 3.5 kV. It mounts on a 35 mm DIN rail, takes three modules, has an optical status indicator and replaceable cartridges. Compliant with EN 50539-11 and EN 61643-11.
Key strengths
Technical specifications
| Feature | Value |
|---|---|
| Product code | 5SD7483-6 |
| Manufacturer | Siemens |
| Type | Combined Type 1+2 surge arrester for DC |
| Maximum continuous operating voltage Ucpv | 1000 V CC |
| Impulse current Iimp (10/350 µs) | 5 kA |
| Nominal discharge current In (8/20 µs) | 15 kA |
| Maximum discharge current Imax (8/20 µs) | 40 kA |
| Voltage protection level Up | 3,5 kV |
| Protection paths | (L+) - (L-) |
| Mounting | 35 mm DIN rail, 53.4 mm wide (3 modules) |
| Status signalling | Optical |
| Protection rating | IP20 |
| Operating temperature | -40 ~ 80 °C |
| Weight | 0,412 kg |
| Certifications | EN 50539-11, EN 61643-11 |
The arrester must be installed as close as possible to the inverter and earthed by the shortest possible path: that is what determines the real protection level.