Mersen gBat fuse 1000V DC
The only NH fuse tested to the standard written for battery circuits
IEC 60269-7 · 100kA breaking capacity · 50A to 250A
The gBat is the NH fuse link tested to IEC 60269-7, the standard written specifically for battery circuits. It is not a photovoltaic fuse pressed into service: it is qualified on the prospective short-circuit currents a lithium bank can really deliver and on the L/R time constants of those circuits, which are far longer than those of a solar string.
The difference reads in one line: 100kA breaking capacity at 1000V DC on the NH1 and NH2 sizes, against the 20kA of an NH gPV of the same format. It is the protection you fit when the bank is large, the specification is serious, or both.
Two contact versions, and the difference matters
The gBat exists with plain blades and with bolted blades. The plain-blade version is the classic NH: it clips into the contacts of a fuse base. The bolted-blade version bolts straight onto the busbar or onto the terminals, with no base, and it is the one that solves the usual problem of compact storage boards, where an NH base simply does not fit. Tell us which one you need when you ask for a quote.
Codes available at 1000V DC
↔ swipe the table sideways
| Size | Reference | Code | Contact |
|---|---|---|---|
| NH1 50A | 10NH1GBAT50 | T1068620 | plain blades |
| NH1 50A | 10NH1GBAT50B | K1068612 | bolted blades |
| NH1 63A | 10NH1GBAT63 | V1068621 | plain blades |
| NH1 63A | 10NH1GBAT63B | L1068613 | bolted blades |
| NH1 80A | 10NH1GBAT80 | W1068622 | plain blades |
| NH1 80A | 10NH1GBAT80B | M1068614 | bolted blades |
| NH1 100A | 10NH1GBAT100 | X1068623 | plain blades |
| NH1 100A | 10NH1GBAT100B | N1068615 | bolted blades |
| NH1 125A | 10NH1GBAT125 | Y1068624 | plain blades |
| NH1 125A | 10NH1GBAT125B | P1068616 | bolted blades |
| NH1 160A | 10NH1GBAT160 | Z1068625 | plain blades |
| NH1 160A | 10NH1GBAT160B | Q1068617 | bolted blades |
| NH2 200A | 10NH2GBAT200 | A1068626 | plain blades |
| NH2 200A | 10NH2GBAT200B | R1068618 | bolted blades |
| NH2 250A | 10NH2GBAT250 | B1068627 | plain blades |
| NH2 250A | 10NH2GBAT250B | S1068619 | bolted blades |
There is also a 1500V DC range, sizes 1XL, 2XL and 3L, up to 500A and up to 200kA breaking capacity, for high-voltage storage systems. Ask us if you need it.
Technical data
| Standard | IEC 60269-7 (gBat) · UL 248-13 |
| Rated voltage | 1000V DC |
| DC breaking capacity | 100kA (NH1 and NH2, L/R up to 3ms) |
| Minimum breaking current | 2×In |
| Rated currents | 50A · 63A · 80A · 100A · 125A · 160A (NH1) · 200A · 250A (NH2) |
| Contact | plain blades or bolted blades for direct mounting |
| Blown-fuse indicator | not provided on this range |
gBat, gPV or Class T
↔ swipe the table sideways
| Mersen gBat | NH gPV 1000V DC | Class T | |
|---|---|---|---|
| Standard | IEC 60269-7, tested on battery circuits | IEC 60269-6, tested on photovoltaic sources | UL standard, born for use on battery banks |
| Rated DC voltage | 1000V (up to 1500V in the extended range) | 1000V | 125V |
| DC breaking capacity | 100kA | 20kA | 20,000A |
| Does it need a base? | no in the bolted-blade version, yes in the plain-blade one | yes, always | yes, a Class T holder or the Lynx Class-T |
| When to choose it | when the specification calls for it, or when the bank is large and you want protection qualified for batteries | when an NH is required and a gBat is not explicitly asked for | 48V installations where the compact format matters more than the rated voltage |
Delivery
- Made to order: lead time and availability confirmed with the quotation
- Shipping within Italy and the European Union
- Tell us the rated current, the contact version and the quantity: we will send you the quotation
ℹ️ Price on request: this item is made to order and the price depends on size, version and quantity. Contact us for a quotation.